Project Overview
Nilima Design Associates carried out a structural health check and Non-Destructive Testing (NDT) assessment of a G+2 residential building at the BPCL Haldia Housing Complex, Haldia, West Bengal – 721631.
Client: Bharat Petroleum Corporation Limited (BPCL). Testing Agency: Nilima Design Associates. Report No.: NDA/HALDIA/24-25/VER01. Report Date: 4 April 2025. Site Observation & Testing: 24 March 2025.
The investigation evaluated the observed condition of columns, beams, slabs and walls, with particular attention to concrete quality, visible distress, reinforcement condition and potential durability concerns.
The assessment combined visual inspection with multiple NDT techniques to develop a broader understanding of the existing structure.
Scope of Investigation
The investigation combined visual inspection and non-destructive testing to assess concrete condition, reinforcement details, visible deterioration and potential durability concerns across selected structural elements.
- Visual inspection of structural elements
- Rebound Hammer testing
- Ultrasonic Pulse Velocity (UPV) testing
- Concrete carbonation testing
- Rebar scanning and Profometer investigation
- Assessment of concrete quality
- Assessment of reinforcement cover and arrangement
- Identification of visible cracks and deterioration
- Technical recommendations for repair and further structural assessment
Visual Structural Inspection
A detailed visual inspection was conducted on the building's structural elements. The inspection recorded cracks in portions of slabs and beams, cracking in different areas of the building, deteriorated plaster at the bottom of slabs and beams, areas of exposed reinforcement, and wall- and plaster-related distress.
The observed concrete condition varied between structural elements. The report particularly noted areas of distress in slab and beam concrete, while the columns were observed to have comparatively better concrete condition.
These observations helped identify locations for subsequent non-destructive testing and further assessment.
- Cracks in portions of slabs and beams
- Deteriorated plaster beneath slabs and beams
- Areas of exposed reinforcement
- Wall and plaster-related distress
- Variation in observed concrete condition between structural elements
Rebound Hammer Testing
Rebound Hammer testing was conducted at selected locations on the building's columns, beams and roof slab to obtain an indication of concrete surface hardness and estimated compressive strength.
The report recorded estimated surface compressive-strength values of approximately 10–34 N/mm² across the tested locations. Several ground-floor columns recorded values around 32–34 N/mm², while selected beams recorded approximately 14–27 N/mm². Several G+2 beams recorded around 13–16 N/mm², and roof-slab locations recorded approximately 10–11 N/mm².
The variation in results indicated that the concrete condition was not uniform throughout the tested structure. The report references IS 13311 (Part 2):1992 for the Rebound Hammer assessment.
Rebound Hammer results provide an indication of surface hardness and estimated compressive strength. They should be interpreted alongside other investigation results rather than treated as a standalone determination of structural capacity.
Ultrasonic Pulse Velocity Assessment
Ultrasonic Pulse Velocity (UPV) testing was carried out to investigate concrete uniformity and identify locations that may contain internal discontinuities.
The reported results ranged from Excellent and Good through Medium to Doubtful, depending on the tested structural element. Some columns recorded relatively high pulse velocities, including 4.609 km/s classified as Excellent, and 4.368 km/s, 4.327 km/s and 4.128 km/s classified as Good.
Several beams recorded significantly lower velocities, including approximately 1.540 km/s, 1.580 km/s, 2.131 km/s and 2.378 km/s, which were classified as Doubtful. Several roof-slab locations were also classified as Doubtful.
The results identified variations in concrete uniformity and specific locations requiring further attention.
- 4.609 km/s — Excellent
- 4.368 km/s — Good
- 4.327 km/s — Good
- 4.128 km/s — Good
- 1.540 km/s — Doubtful
- 1.580 km/s — Doubtful
- 2.131 km/s — Doubtful
- 2.378 km/s — Doubtful
Carbonation Assessment
Carbonation testing was performed to assess the condition of the concrete cover and its potential effect on reinforcement protection.
The report recorded significant carbonation at the tested locations and raised concerns regarding the protective passivation layer surrounding the reinforcement. Carbonation can reduce concrete alkalinity and increase the potential for reinforcement corrosion when the carbonation front reaches the reinforcement.
Rebar Scanning & Concrete Cover Assessment
Rebar scanning was carried out using a Profometer or cover meter to investigate approximate concrete cover, reinforcement diameter, reinforcement spacing, stirrup arrangement and reinforcement percentage.
The investigation covered selected columns, beams and slabs. Selected column locations showed approximately 39–49 mm of concrete cover, while reinforcement arrangements and spacing were recorded for the inspected members. Beam and slab reinforcement information was also documented in the report.
The investigation provided additional information for understanding the existing RCC construction and assessing areas where deterioration had been observed.
- Approximate concrete cover measurement
- Reinforcement diameter assessment
- Reinforcement spacing investigation
- Stirrup arrangement assessment
- Reinforcement percentage documentation
Key Findings
The combined investigation identified variable concrete condition across the structural elements, visible cracking and deterioration in portions of beams and slabs, areas of plaster deterioration with exposed reinforcement, doubtful UPV results at selected locations, and significant carbonation requiring attention to reinforcement durability.
The results indicated that the condition of the investigated concrete was not uniform and that selected elements required further assessment and appropriate repair or rehabilitation.
- Concrete condition: Variable Rebound Hammer values and doubtful UPV results at selected locations.
- Structural distress: Visible cracks and deterioration in portions of beams and slabs.
- Reinforcement exposure: Plaster deterioration and exposed reinforcement in some areas.
- Internal concrete condition: Doubtful UPV classifications at selected beams and slab locations.
- Carbonation: Significant carbonation reported at tested locations, raising durability concerns.
Recommended Rehabilitation Measures
The report recommended appropriate repair and rehabilitation measures based on the observed distress and NDT findings. The repair approach should be selected according to the condition and extent of deterioration at each location.
- Epoxy grouting: Apply to identified cracks and damaged areas where appropriate, in accordance with the repair design and material specifications.
- Corrosion protection: Where reinforcement is exposed, carefully expose and clean the reinforcement, remove loose corrosion products, apply a suitable corrosion-inhibiting treatment, and reinstate the protective concrete cover using an appropriate repair material.
- Concrete repair: Remove damaged or deteriorated concrete and repair the affected areas following suitable surface preparation.
- Waterproofing and moisture control: Treat areas exposed to water ingress to help reduce continued moisture-related deterioration.
- Structural monitoring: Conduct follow-up inspections after repair works to evaluate the effectiveness of rehabilitation and monitor the condition of the structure.
Engineering Assessment
This project demonstrates why visual inspection alone may not be sufficient when evaluating an existing RCC building. At the BPCL Haldia Housing Complex, each investigation technique provided different information about the condition of the structure.
Visual inspection identified cracks, plaster deterioration and exposed reinforcement. Rebound Hammer testing provided an indication of surface concrete strength, while UPV testing identified variations in concrete uniformity and doubtful locations.
Carbonation testing provided information regarding carbonation and reinforcement protection, while rebar scanning supplied information about reinforcement location, cover and arrangement.
Combining these investigations supported a more comprehensive assessment of the building's observed condition and helped identify locations requiring attention.
- Visual Inspection — Identification of visible distress and deterioration.
- Rebound Hammer — Indication of concrete surface hardness and estimated compressive strength.
- UPV Testing — Assessment of concrete uniformity and identification of doubtful locations.
- Carbonation Testing — Assessment of carbonation and its potential implications for reinforcement protection.
- Rebar Scanning — Investigation of reinforcement location, cover and arrangement.
Conclusion
The assessment documented visible distress and variable concrete condition within the investigated building. Several locations, particularly portions of beams and slabs, showed lower NDT values and/or doubtful UPV classifications.
The report recommended structural assessment and repair or rehabilitation measures, including epoxy grouting where appropriate, corrosion treatment, concrete repair, waterproofing where required and continued structural monitoring.
The findings demonstrate the importance of combining non-destructive testing, visual inspection and engineering assessment when evaluating an existing RCC structure.
Our Approach
INSPECT → TEST → ANALYSE → ASSESS → REPAIR → MONITOR
Nilima Design Associates provides integrated Structural Health Assessment, NDT Testing, Rebar Scanning, UPV, Rebound Hammer, Carbonation Testing and Structural Rehabilitation Consultancy for existing buildings and infrastructure.
More field notes and case studies are on the way.